Calculating the Maximum Duct Run Length
The maximum straight duct length for the hood is 50 feet.
To determine the actual maximum duct run, subtract the
equivalent length of each elbow, transition and cap from
50 feet.
EQUIVALENT LENGTHS
Piece Subtract Piece Subtract
8” 90° elbow 7 feet
10” 90°
elbow
5 feet
8” 45° elbow 3 feet
10” 45°
elbow
2 feet
3¼” X 10”
to round 90°
transition
25 feet
3¼” X 10” to
8”/10” round
transition
4 feet
Roof cap *
Wall cap
with damper
*
* The equivalent lengths of roof and wall caps vary with
model and configuration. For equivalent length, contact
the manufacturer or a qualified HVAC specialist.
Installation Specifications
Duct Work Design Tips
Wherever possible, reduce the number of transitions and
turns to as few sharp angles as possible. Two staggered
45° angles are better than one 90°.
Keep turns as far away from the hood exhaust as pos-
sible, and as much space between bends as possible.
For best performance, use round duct instead of rectan-
gular, especially when elbows are required.
If multiple elbows are used, try to keep a minimum of 24
inches straight duct between them.
Avoid “S” or “back to back” use of adjacent elbows.
In regions where the weather gets extremely cold, use
thermal breaks, such as a short section of non-metallic
duct, to avoid indoor heat loss. Locate the break as close
as possible to the outside pass through point.
Do not use flexible metal duct.
DO NOT use duct work that is smaller in cross-sectional
area than the recommended types above.
Installation Instructions
Verify the Package Contents
Unpack the parts boxes and verify that all required com-
ponents have been provided. The parts shown below
include the contents of the chimney kit (DHICH),
which is required for installation. If any item is missing
or damaged, please contact the dealer immediately. Do
not install a damaged or incomplete appliance.
Hood assembly with filter(s)
Chimney assembly (2 piece)
Mounting bracket
Blower exhaust cowling (2 blower units only)
Framework assembly (2 piece)
Mounting and assembly hardware
Product literature
A
A
B
C
C
B
D
D
E
F
F
G
E
G